In Canada, many commercial and industrial buildings are fed by a 347/600V three-phase system, so lighting runs at 347V line-to-neutral. Choose fixtures marked 120-347V (universal voltage) and they will work on 120V, 277V and 347V circuits. Always confirm the voltage range on the fixture label before you order or install.
Why is 347V common in Canadian commercial buildings?
Larger Canadian commercial and industrial buildings are often supplied with a 600V three-phase service. Between any one phase and neutral on that system you get 347V, which is a convenient voltage for lighting circuits because it keeps current low over long runs.
The result is that warehouses, schools, retail plazas, parkades and industrial plants frequently have lighting panels at 347V. Smaller buildings, offices with 208V service and most homes use 120V instead. The only reliable way to know is to check the panel schedule or ask the electrician or the building owner.
What does a 120-347V universal fixture mean?
A 120-347V rating means the LED driver accepts any input voltage in that range. One fixture can be installed on a 120V, 277V or 347V circuit without changing the driver or the wiring.
For distributors and contractors, universal voltage has real practical value:
- One part number covers several buildings, so you stock fewer variations.
- A fixture ordered for the wrong voltage is no longer a problem on most jobs.
- Replacements and future retrofits are simpler because the driver tolerates the circuit it lands on.
Not every fixture is universal. Some products are 120V only, 120-277V, or higher-voltage units for 347V and 480V circuits. Treat the label as the final word.
What is the difference between 347V and 277V?
277V is the line-to-neutral voltage on the 480Y/277V system used for commercial lighting in the United States. 347V is the line-to-neutral voltage on the 600Y/347V system used in Canada. They are different systems, and a fixture rated only for 277V is not suitable for a 347V circuit.
| Rating |
Typical use |
Works on 347V? |
| 120V only |
Homes, small commercial, some 120V branch circuits |
No |
| 120-277V |
Common US-market commercial fixtures |
No, check carefully |
| 277V only |
Commercial buildings on a 480Y/277V system |
No |
| 120-347V |
Canadian commercial and industrial buildings |
Yes |
| 347V or 347-480V |
Buildings that use only 347V or 480V lighting circuits |
Check the label for the exact range |
This is the main reason to be careful with imported or online fixtures. A product listed as universal in the US may stop at 277V, and a driver connected above its rating can fail immediately.
How do you check a fixture for 347V?
Do it before the fixture goes on a lift. The label and the spec sheet will tell you everything you need.
- Find the input voltage on the fixture or driver label. Look for a range such as 120-347V or 120-277V.
- Confirm that 347V falls inside the range, not just near it.
- Confirm the voltage of the circuit at the panel or with the electrician before energizing.
- Check that any sensor, emergency battery pack or control accessory is rated for the same voltage.
- Check the Canadian Electrical Code and your local authority having jurisdiction (inspector) for approvals and wiring requirements.
Can you use sensors and dimming on 347V circuits?
Yes, but each component has to be rated for the circuit. Many LED drivers use a 0-10V dimming input. That control signal is low voltage and separate from the line voltage, so a 0-10V dimmer or sensor can control a fixture on a 347V circuit as long as the driver supports it.
Items that connect to line voltage are different. A sensor that sits in the power path, a battery backup or a line-voltage switch must be rated for 347V. Do not assume that a 120V or 277V accessory is acceptable. For sensor-ready high bays and similar products, check the product page for the sensor type and its voltage rating.
When is 120V used instead?
Some Canadian commercial spaces run lighting on 120V. This is common in smaller offices, retail units, restaurants, residential-style common areas and tenant spaces fed from a 120/208V panel. Renovation jobs may mix both.
A fixture rated 120-347V works in these spaces too, which is why contractors who work across several building types often standardize on universal voltage. Where you are matching an existing fixture, check the existing circuit voltage rather than guessing from the building type.
Which LitesGo products come in 120-347V?
Many commercial and industrial fixtures are available with wide-voltage drivers. Browse these collections and check the voltage range on each product page:
For project help in Alberta, see our commercial lighting supply in Edmonton. Contractor accounts with Net 30 terms are available, subject to approval.
Frequently asked questions
What voltage is 347V used for in Canada?
347V is the line-to-neutral voltage on a 600Y/347V three-phase system. It is widely used for lighting in Canadian commercial and industrial buildings.
Can a 120-277V fixture run on 347V?
No. A 120-277V driver is not rated for 347V, and connecting it to a 347V circuit can damage the driver. Choose a fixture marked 120-347V or higher.
Is 347V the same as 277V?
No. 277V is from the 480Y/277V system common in the United States, and 347V is from the 600Y/347V system common in Canada. They are not interchangeable.
Can I dim a 347V fixture with a standard 0-10V dimmer?
Usually yes. The 0-10V signal is low voltage and independent of the line voltage, so it works on a 347V fixture if the driver has a 0-10V dimming input. Confirm this on the product page.
How do I know which voltage my building has?
Check the panel schedule or the label on the panel, or ask the electrician or building owner. If you are unsure, have a licensed electrician measure the circuit before you order fixtures.
Need help matching fixtures to your building voltage? Contact the LitesGo team or call (587) 701-5969. We are at 4914 89 St NW, Edmonton, AB T6E 5K1, and in-stock items usually dispatch in 1-2 business days anywhere in Canada.